J80U Power Products Generating set, equipped with a JOHN DEERE engine and MECC ALTE alternator.

ORDER

General Specification

Engine Specification

Alternator Specification

Dimensions

Control Panels

 

General Specification

General Characteristics

Engine type 4045TF220
Alternator type ECP34-2VS-F12
Performance class G3
Frequency (Hz) 60
Reference voltage (V) 480/277
Max power ESP (kVA) 100
Max power ESP (kWe) 80
Max power PRP (kVA) 90.90909090909090
Max power PRP (kWe) 72.72727272727270
Intensity (A) 120
Standard Control Panel NEXYS
Optional control panel TELYS
Optional Control Panel N/A
Optional control panel N/A

Descriptive

Mechanic governor
Mechanically welded chassis with antivibration suspension
Main line circuit breaker
Radiator for wiring temperature of 48/50°C max with mechanical fan
Protective grille for fan and rotating parts
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
12 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation

Power

Voltages ESP PRP Back-up
power
kWe kVA kWe kVA
480/277 80 100 73 91 120
440/254 78 98 71 89 129
220/127 78 98 71 89 257
208/120 74 92 67 84 255

Engine Specification

GENERAL ENGINE DATAS

Engine model JOHN DEERE
Engine type 4045TF220
Air inlet Turbo
Air coolant N/A
Number of cylinders 4
Cylinder arrangement L
Displacement (C.I.) 4.48
Bore (mm) 106
Stroke (mm) 127
Compression ratio 17 : 1
Speed (RPM) 1800
Pistons speed (m/s) 7.62
Maximum stand-by power at rated RPM (kW) 93
Frequency regulation (%) +/- 2.5%
BMEP (bar) 12.50
Governor type Mechanical

EXHAUST

Exhaust gas temperature (°C) 530
Exhaust gas flow (L/s) 280
Max. exhaust back pressure (mm EC) 750

FUEL

Fuel consumption 110% load (L/hr) 23
Fuel consumption 100% load (L/hr) 21
Fuel consumption 75% (L/h) 16
Fuel consumption 50% (L/h) 11.50
Maximum fuel pump flow (L/h) 112

OIL

Oil capacity (L) 13.50
Min. oil pressure (bar) 1
Max. oil pressure (bar) 5
Oil consumption 100% load (L/h) 0.021
Carter oil capacity (L) 12.50

HEAT BALANCE

Heat rejection to exhaust (kW) 69
Radiated heat to ambiant (kW) 10
Haet rejection to coolant (kW) 46

AIR INTAKE

Max. intake restriction (mm EC) 625
Intake air flow (L/s) 115

COOLING SYSTEM

Radiator & Engine capacity (L) 23.60
Max water temperature (°C) 105
Outlet water temperature (°C) 93
Fan power (kW) 4.30
Fan air flow w/o restriction (m3/s) 3.71
Available restriction on air flow (mm EC) 20
Type of coolant Glycol-Ethylene
Thermostat (°C) 82-94

EMISSIONS

Emission PM (g/kWh) N/A
Emission CO (g/kW.h) N/A
Emission HCNOx (g/kWh) N/A
Emission HC (g/kW.h) N/A

Alternator Specification

General datas

Alternator brand MECC ALTE
Alternator type ECP 34 2VS/4
Number of phase 3
Power factor (Cos Phi) N/A
Altitude (m) 0 à 1000
Overspeed (rpm) 0
Number of pole 4
Excitation system AVR
Insulation class H
T° class, continuous 40°C N/A
Regulation DSR
Harmonic factor, no load TGH/THC (%) N/A
Wave form : NEMA=TIF-(TGH/THC) N/A
Wave form : CEI=FHT-(TGH/THC) N/A
Number of bearing 1
Coupling Direct
Voltage regulation at established rating (%) N/A
Recovery time (Delta U = 20% transcient) (ms) N/A

Other datas

Continuous Nominal Rating 40°C (kVA) 80
Standby Rating 27°C (kVA) N/A
Efficiencies 4/4 load (%) 93
Air flow (cfm) 0.233
Short circuit ratio (Kcc) 0.49
Direct axis synchro reactance unsaturated (Xd) (%) 330
Quadra axis synchro reactance unsaturated (Xq) (%) 184
Open circuit time constant (T''do) (ms) 1300
Direct axis transcient reactance saturated (X''d) (%) 22
Short circuit transcient time constant (T''d) (ms) 40
Quadra axis subtranscient reactance saturated (X""q) (%) 30.60
Subtranscient time constant (T""d) (ms) 5.10
Quadra axis subtranscient reactance saturated (X""q) (%) 30.60
Zero sequence reactance unsaturated (Xo) (%) 4.10
Negative sequence reactance saturated (X2) (%) 21.50
Armature time constant (Ta) (ms) 14
No load excitation current (io) (A) 0.38
Full load excitation current (ic) (A) 2.10
Full load excitation voltage (uc) (V) 0
Recovery time (Delta U = 20% transcient) (ms) N/A
Motor start (Delta U = 20% perm. or 50% trans.) (kVA) 0
Transcient dip (4/4 load) - PF : 0,8 AR (%) 0
No load losses (W) 0
Heat rejection (W) 5781

Dimensions

DIMENSIONS COMPACT VERSION

Length (mm) 1870
Width (mm) 994
Height (mm) 1360
Dry weight (kg) 1056
Tank capacity (L) 180

DIMENSIONS SOUNDPROOFED VERSION

Canopy M128
Length (mm). 2300
Width (mm). 1060
Height (mm). 1680
Dry weight (kg). 1462
Tank capacity (L). 180
Acoustic pressure level @1m in dB(A) 83
Acoustic pressure level @7m in dB(A) 73

CONTAINMENT

Canopy M128 DW
Length (mm). 2344
Width (mm). 1060
Height (mm). 1900
Dry weight (kg). 1709
Tank capacity (L). 390
Acoustic pressure level @1m in dB(A) 83
Acoustic pressure level @7m in dB(A) 73

Control Panels

NEXYS, comprehensive and simple

The NEXYS is a versatile control unit allowing operation in manual or automatic mode. Equipped with an LCD screen, the user-friendly NEXYS offers high-quality basic functions to guarantee simple, reliable operation of your generating set.

Offers the following functions:

Standard electrical measurements: voltmeter, frequency meter, ammeter.
Engine parameters: working hours counter, engine speed, battery voltage, fuel level.
Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed (> 60 kVA), charging alternator fault, low fuel level, emergency stop.

TELYS, ergonomic and user-friendly

The highly versatile TELYS control unit is complex yet accessible, thanks to the particular attention paid to optimising its ergonomics and ease of use. With its large display screen, buttons and scroll wheel, it places the accent on simplicity and communication.

The TELYS offers the following functions:

Electrical measurements: voltmeter, frequency meter, ammeter.
Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage.
Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop, fuel level.
Ergonomics: wheel for navigating around the various menus.
Communication: remote control and operation software, USB connections, PC connection.